Service Hotline:+86-13816217984
CONTACT US/ CONTACT US
Service Hotline +86-13816217984
Standard Groups

Email:info@standard-groups.com

Landline:+86(21)-64208466

Telephone:+86-13816217984

Address:Unit 3A, 20/F,Far East Consortium Building,121 Des Voeux Road Central, Hong Kong

Location:home > Product > Other Equipment

Other Equipment

3 Metre Cube Smoke Density Tester

None halogen cables and materials are required to measure smoke density; the main principles of the smoke density is measured in a particular space, cable or material in a particular combustion or radiation condition, which will produce smoke, the light b...

Consult NowConsult Now

hotline :+86-13816217984

WeChat:+86-13816217984email:info@standard-groups.com Standard Groups

Product details

None halogen cables and materials are required to measure smoke density; the main principles of the smoke density is measured in a particular space, cable or material in a particular combustion or radiation condition, which will produce smoke, the light beam will decay after passing through the smoke,so the light density and smoke density can be calculated by measuring the light transmittance.

TESTECH Wire and Cable Smoke Density Tester comply with  IEC61034-1 ~ 2: 1997"Measurement of smoke density of cables and optical cables under specified conditions".It is used for the measuring power transmission signal or all insulated metallic conductor cables under specific conditions is horizontal burning emitted smoke the transmission rate of the test.The standard IEC 61034 requires smoke box size is 3M³.

Standards

• IEC61034

Structural features:

1. The box is composed of a cube shell with long, wide and high 3000mm + 30mm,and the internal material is SUS 304 stainless steel;

2. The internal toolings are all made of stainless steel,corrosion-resistant;

3. The total area of the vent is 50cm2 ± 10cm2. it is opened during the test,baffle height is 1000mm;

4. Equipped with wire and cable test stands and hang-heavy weights according to standard requirements;

5. Test room has a glass observation window on the door,and the opposite side of the door is provided with a sealed transparent window (minimum 100mmx100mm), which can transmitting light for the measurement system.It's about 2150mm+100mm high from the ground;

6. Photocell and the light source is positioned at the center of each window on two walls;

Smoke Density Test System:

1.Llight source: clean crystal lamps and tungsten halogen lamps, 2900K color temperature; power 100W, DC12V, nominal luminous flux 2000lm ~ 3000lm;

2. Smoke density test: measured optical density range of 0% to 100%;

3. Special light source of smoke density and high resolution photoelectric tube receiver can be installed on the external wall;

4. Test room equipped with doors and windows sealed structure;

5. The standard power is 100W and voltage is DC 12V for the light source;

6. Optical calibration system: 0 to 100% point calibration;

Combustion sources:

1. Ethanol 90% ± 1%; methanol 4% ± 1%; water, 6% ± 1%;

2. Alcohol burning box;

3. The distance between alcohol burning box and the ground is 100mm + 10mm;

Control systems:

1. The computer control system, Labview special test software; artificial intelligence control interface,

2. Power regulator precision is ±0.01V

3. Automatic ignition system, automatic timing;

4. Experimental data can be automatic storage, are free to query;

5. With timing reminders;

Specification:

Model STD-IEC61034
Size 3.450(W)×3.160(D)×3.450(H)mm
Table size 600(W)×750(D)×1.600(H)mm
Power AC 220V, 50/60Hz, 20A
Weight 2.500kg
Manual Provided
Other requirements Computers, compressed gases, vacuum cleaner
tags:

Related

Name*

Phone Number*

Messages:

Service Hotline

Service Hotline

+86(21)-64208466

WhatsApp
Standard Groups
Top
XStandard Groups

WhatsApp

WhatsApp:+86-13816217984

(点击微信号复制,添加好友)

  WhatsApp

WhatsApp!