— Product —
Service Hotline +86-13816217984 Email:info@standard-groups.com
Landline:+86(21)-64208466
Telephone:+86-13816217984
Address:Unit 3A, 20/F,Far East Consortium Building,121 Des Voeux Road Central, Hong Kong
Flame-retardant building materials
The Building Material Flammability Test Furnace assesses how easily building materials ignite and sustain burning under specific conditions, crucial for fire safety classification....

Enquire NowEnquire Now
Phone Number :+86-13816217984
WhatsApp:+86-13816217984Email:info@standard-groups.comProducts
Touch screen control building materials flammability test furnace adopts stainless steel box, is in the old JCK-2 products based on the new touch screen control sample controlled automatic lifting, Bunsen lamp can adjust the function of the upgrade product, is strictly in accordance with the national standard GB8626-2007 and the production of high configuration building materials combustion grade test instrument.
Building materials flammability test furnace is in the normal combustion environment, with a small flame directly impact vertically placed samples to determine the flammability of building products Building materials flammability test furnace using the German KLEINBRENNER(Kleinbrenner) principle, in the vertical direction of the small flame direct impact, It is used to determine the combustion performance of Class B building materials (that is, it is used to determine the combustion performance of building materials/flame retardant grade B)
In the construction industry, the flammability of building materials is crucial for building safety. Building material flammability testing furnaces can be used to test the flammability of various building materials, thereby improving building safety. This provides quality assurance for manufacturers. By testing the flammability of products, it ensures that products meet national standards and customer requirements, enhancing the competitiveness of enterprises. It is an important technical means for quality inspection agencies to test building materials. By testing the flammability of building materials, their safety and reliability can be assessed, thus guaranteeing building safety. The building material flammability testing furnace is of great significance in ensuring building safety and production quality: Through testing with the building material flammability testing furnace, companies can gain insights into product improvement and upgrading. Based on experimental data, more scientific and reasonable raw material ratios and production processes can be developed, improving product quality and competitiveness. It effectively assesses the flammability of building materials, facilitating the development of more detailed building codes and standards by relevant departments. At the same time, it allows for the prohibition and replacement of highly flammable building materials, thus improving building safety.
IS011925-2:2002E "Test Method for Flammability of Building Materials"
GB/T8626-2007 "Combustibility test Method for Building Materials"
Technical parameters:
| Stainless steel plate box | 1.5mm |
| Bunsen burner | can be adjusted forward and backward |
| Diameter of burner | Φ 0.17mm burner with regulator; four ¢4mm air suction inlet |
| Flame length of Bunsen burner | 20mm ± 2mm |
| Ignition source | can be automatically tilted by 45 degrees |
| The Bunsen burner applies a flame time | 15s to the pattern |
| Flame height | Adjusted by precision adjustment valve |
| Sample rack | can move up and down and back and forth |
| Sample holders | 2 pcs |
| Touch screen display | 7 inches Effective display size 15.5cm in length and 8.6cm in width |
| Resolution | 800 * 480 |
| Communication interface | RS232. 3.3V CMOS or TTL, serial port mode |
| Storage capacity | 1G |
| FPGA driver display | "zero" start time, can run after power on |
| Controller | adopts low energy consumption processor, and automatically enters energy saving mode |
| Gas source | >95% propane gas;(user should provide for themselves) |
| Gas pressure | 10kpa~50kpa |
| Flue air velocity | 0.7m/s only on condition of burner burning and draught hood open |
| Time adjustment of continuous flame | 0 ~ 99minutes99seconds |
| Time adjustment of afterflame | 0 ~ 99minutes99seconds |
| Timer accuracy | ≤1s/h |
| Ambient temperature | 15 ℃ ~ 25 ℃; |
| Relative humidity | ≤ 85% |
| Cabinet size | 835 × 400 × 815mm |
| Power supply voltage and power | 220 V, 50 Hz, 100 W |
1. Building Material Flammability Tester 1 unit
2. Power cord 1 piece
3. Gas pipe (with clamp) 1 piece
4. Clamps 2 sets
5. Flame height measuring device 1 unit
6. Flame positioner 2 units
7. Stainless steel wind speed device (optional) 1 set
8. Product manual 1 copy
9. Product certificate of conformity 1 piece
I. Equipment Installation and Preparation
Accessory Check: Confirm that the included accessories include the sample holder, positioning device, drip tray, flame ruler, gas valve, and gas pipe. If a wind speed device is selected, an additional power supply needs to be connected, and the wind speed should be adjusted to 0.7 ± 0.1 m/s.
Gas and Power Connection: Install the valve onto the gas cylinder (the safety valve needs to be opened manually), and connect the equipment's power and gas supply. If a wind speed meter is equipped, calibrate the airflow direction and insert it into the temperature measurement port.
II. Operating Procedure
Parameter Settings: Set the experiment time (usually 15 seconds or 30 seconds) via the touchscreen interface, and select whether to enable the "automatic ignition" or "automatic gas shut-off at the end of the experiment" function.
Sample Installation: Use the sample holder to fix the material (usually 250mm × 90mm), and adjust the flame contact position using the positioning device (e.g., 40mm from the bottom edge).
Flame Adjustment: Start the gas and ignite the flame, adjust the Bunsen burner to a 20 ± 2mm blue flame, and tilt it 45 degrees towards the sample.
III. Experiment Execution and Observation
Start Experiment: After clicking "Start," the burner contacts the sample and the countdown begins. Observe the combustion phenomena (e.g., surface ignition, burning to the marked line).
Data Recording: Save the data after the experiment, turn off the gas, and check the sample's combustion status (e.g., remaining length, whether dripping material ignites the filter paper).
IV. Safety and Maintenance
Operating Procedures: Avoid putting hands into the test furnace, and do not stack flammable materials around the equipment. Stop the machine immediately in case of any abnormalities.
Regular Calibration: Calibrate the heat load uniformity (4-point temperature difference ≤ 15℃) and wind speed (5-point measurement error ≤ 10%) every 3 months.